Technical Parameters:
AC Voltage Regulation Accuracy: 0.25%, THDu < 5%.
Overall Dimension 153mm x 138mm x 61mm
Working Temperature (-40~+70)°C
Working Humidity (20~95)%RH
Storage Temperature (-40~+85)°C
Weight 0.7kg
Installation Fixed by screws
IP Rating IP20
Product Overview:
HVR620 Digital Voltage Regulator is used to adjust the field current of brushless AC synchronous generator, which can be applied to generators with the excitation system of PMG, AUXW or SHUNT. The excitation regulation mode of the regulator is automatic voltage regulation (AVR). It has USB interface and CAN BUS interface.
The product adopts 32-bit micro-processor technology, which can achieve precision measurement of multiple parameters, protection threshold adjustment, real-time data monitoring and analysis, flexible and comprehensive fault protection, etc. All parameters can be read and configured on PC via USB interface. And it features compact structure, simple connections and high reliability.
PERFORMANCE FEATURES
Main features are as following:
- Excitation regulation mode: automatic voltage regulation (AVR);
- Over-excitation limit, U/F limit function is fitted;
- Soft start function is fitted;
- PID algorithm for excitation regulation;
- Three ways to adjust voltage: potentiometer, parameters configuration on PC, CAN communication;
- Excitation power supply: voltage input is (100-277) VAC (1P2W) or DC voltage;
- Continuous field current is 4A, maximum short-time current is 7.5A for 10s;
- With load compensation function (LCF);
- Suitable for AC systems of 3P3W, 3P4W, 2P3W and 1P2W at rate frequency between 10Hz and 200Hz;
- Detect generator voltage harmonic THDu, and 1st-15th odd harmonic;
- The measured generator voltage represents a true RMS value;
- Collect excitation voltage, field current, generator voltage, frequency, etc.;
- Function of heat sink temperature detection and alarm protection;
- Function of winding temperature detection and alarm protection;
- Protection and detection function: gen. over/under voltage, gen. over/under frequency, gen. unbalanced voltage, gen. harmonic distortion, gen. unavailable, excitation over voltage, excitation overcurrent, rotating diode fault, etc.;
- Real-time data curve analysis can be done to adjust PID parameters via PC software;
- All parameters can be configured on PC via USB interface;
- Data monitoring can be realized via the CAN communication interface;
- It can be applied to all types of brushless AC synchronous generators with the excitation system of PMG, AUXW, or SHUNT;
- Event log function can cyclically record 999 events based on the running time;
- Black box function enables it to record 5 groups of fault alarm data cyclically;
- Modular design, pluggable terminal, screw fixing, compact structure and easy installation.