Technical Parameters:
Working Voltage DC8.0V to DC35.0V, continuous power supply
Power Consumption <5W(Standby mode: ≤3W)
AC Voltage Input:
3P4W 15V AC ~ 360 V AC (ph-N)
3P3W 30V AC ~ AC620 V AC (ph-ph)
1P2W 15V AC ~ AC360 V AC (ph-N)
2P3W 15V AC ~ AC360 V AC (ph-N)
AC Alternator Frequency 50Hz/60Hz
Speed Sensor Voltage 1.0V to 24V (RMS)
Speed Sensor Frequency 10,000 Hz (max.)
Start Relay Output 16A DC28V DC supply output
Fuel Relay Output 16A DC28V DC supply output
Aux. Output 1 7A DC28V DC supply output
Aux. Output 2 7A AC250V Volts free output
Aux. Output 3 16A AC250V Volts free output
Aux. Output 4 16A AC250V Volts free output
Voltage Input of Battery Pack 0V DC ~100 V DC
Overall Dimensions 209mm x 167mm x 45mm
Panel Cutout 186mm x 141mm
C.T. Secondary Current Rated:5A
Working Temperature (-25~+70)ºC
Working Humidity (20~93)%RH
Storage Temperature (-30~+80)ºC
Protection Level IP65: when water-proof gasket installed between control panel and
enclosure.
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal and low
voltage terminal. The leakage current is not more than 3mA within
1min.
Weight 0.732kg
Product Overview:
HGM6120T Genset Controller is a power generation control module developed for mobile communication base station and the functions of the controller are set according to the actual situation of the mobile base station. The controller is equipped with multi functions of auto start/stop, data measurement, alarm protection, etc. It also can monitor the room temperature and battery voltage to achieve the goal of ATS automatic transfer of mains supply/load and mains supply/air conditioner.
HGM6120T Genset Controller integrates digital, intelligent and network technology, which is used for the automation and monitoring system of single unit, realizing the automatic start/stop, data measurement, alarm protection and “three remotes” functions. The controller adopts LCD display, optional interfaces of Chinese and English with easy and reliable operation.
HGM6120T Genset Controller adopts microprocessor, realizes the precision measurement, value adjustment, timing and threshold setting etc. All the parameters can be adjusted from the front panel or by USB interface (or RS485 interface) of PC to adjust and monitor. It can be widely used in all types of automatic control systems for its compact structure, simple connections and high reliability.
HGM6120T Genset Controller has a built-in network communication module, which can realize genset access to internet. After controller logging in cloud server, the unit data information (including GPS positioning, altitude, etc.) will be uploaded in real time to the corresponding cloud server. Users can monitor the genset and inquire the genset running status and the event log, as well as configure the parameters via cloud server by phone APP (ISO or Android), computer and terminal equipment. The network communication module also has SMS function.
PERFORMANCE AND CHARACTERISTICS
132 x 64 LCD display with backlight, optional language interfaces (Chinese and English), push-button operation;
Acrylic screen, improved wearable and scratch resistance property;
Silica-gel panel and keys can well adapt to higher and lower temperatures;
With RS485 communication interface, which can achieve “three remotes” functions via MODBUS protocol (available for the controller with RS485 interface);
With CANBUS interface, which can be connected to ECU with J1939, it not only can monitor common data (such as water temperature, oil pressure, speed and fuel consumption, etc.), but also can control start/ stop, high/low speed (controller with CANBUS interface is needed) via CANBUS interface;
Suitable to 3P4W, 3P3W, 1P2W and 2P3W (120V/240V) power supply, 50Hz/60Hz system;
Collect and display 3-phase voltage, 3-phase current, frequency, power parameter of mains supply/Gen;
Mains Gen
Line voltage (Uab, Ubc, and Uca) Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc) Phase voltage (Ua, Ub, and Uc)
Frequency HZ Frequency HZ
Phase Sequence Phase Sequence
Load
Current IA, IB, IC
Phases and Total Active Power kW
Reactive power kvar
Apparent power kVA
Power factor PF
Generator accumulated energy kWh
Output percentage with load %
Mains supply has functions of over/under voltage and loss of phase; Gens has functions of over/under voltage, over/under frequency, over current and over power;
Precision measurement and display of parameters about engine,
Temp. (WT), °C/ °F
Oil pressure (OP), kPa/psi/bar
Fuel level (FL), % Fuel remains L
Speed (SPD), r/min
Battery Voltage (VB), V
Charger Voltage (VD), V
Accumulative running hours
Accumulative start times
Can collect the room temperature and control the starting of air conditioner when temperature is too high;
Can collect the voltage of battery pack (48V), when