Technical Parameters:
Working PowerRange : DC(8~35)V
Overall Dimension : 135*114*44
Installation Dimension : 116*90
Working Temperature : (-25~+70)℃
weight : 0.32kg
Product Overview:
HGM4000N-DC series genset controllers integrate digital, intelligent and network technology which are used for automation and monitoring system of single generator set to achieve functions of automatic start/stop, data measurement, alarm protection, etc. The series can be applied for AC gensets and DC gensets. It fits with LCD display, optional languages interface (Chinese, English, Spanish, Russian, Turkish, French, Portuguese, and Polish), and it is reliable and easy to use.
HGM4000N-DC series genset controllers adopt micro-processor technology with precise parameters measuring, fixed value adjusting, time setting and set value adjusting, etc. All parameters can be configured on the front panel or through the programmable interface (USB or RS485 interface) via PC. It can be widely used in all types of automatic genset control system with compact structure, simple connections and high reliability.
PERFORMANCE AND CHARACTERISTICS
HGM4000N-DC series controller has three models:
HGM4010N-DC/HGM4010NC-DC/HGM4010CAN-DC: It is used for automation of single generator set, which controls generator set to start/stop automatically via remote signal.
Main features as follows:
➢ 132x64 LCD with backlight, selectable language interface (Chinese, English, Spanish, Russian, Turkish, French, Portuguese, and Polish), press the button to operate.
➢ Hard-screen acrylic material is used to protect screen with great wear-resisting and scratch-resisting functions.
➢ Silicone panel and pushbuttons can be used in extreme temperature environment.
➢ RS485 communication interface enables “Three remote” functions (remote control, remote measuring and remote communication) according to MODBUS protocol.
➢ Equipped with CANBUS port and can communicate with J1939 genset. Not only can monitor frequently-used data (such as water temperature, oil pressure, speed, fuel consumption and so on) of ECU machine, but also control starting up, shutdown, raising speed and speed droop via CANBUS port (need controller with CANBUS interface).
➢ Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with voltage 120/240V and frequency 50/60Hz, and it is compatible with DC power supply system;
➢ Collects and shows 3-phase voltage, current, power parameter and frequency of generator.
Generator
Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc)
Frequency Hz
Phase sequence
Load
Current Ia, Ib, Ic A (unit)
Each phase and total active power P kW (unit)
Reactive power Q kvar (unit)
Apparent power S kVA (unit)
Power factor PF
Accumulated generator power W kWh, kvarh, kVAh (unit)
Output percentage with load %
➢ For generator, the controller has over/under voltage, over/under frequency, over current and over power detection functions.
➢ Precisely measure and display parameters about engine.
Temp. (WT) °C/°F
Oil Pressure (OP) kPa/psi/bar
Fuel Level (FL) % Fuel Quantity Left L (unit)
Speed (RPM) r/min (RPM)
Voltage of Battery V
Voltage of Charger V
Hour count accumulation
Start times accumulation
➢ Protection: automatic start/stop of the genset, ATS (Auto Transfer Switch) control with perfect fault indication and protection function.
➢ With ETS (energize to stop), idle control, pre-heat control and raise/drop speed control functions, which are all relay outputs.
➢ Parameter setting: parameters can be modified and stored in internal FLASH memory and cannot be lost even in case of power outage; most of them can be adjusted using front panel of the controller and can be modified using PC via USB or RS485 port.
➢ With multiplex input port 4 and 5. Input port 4 can be configured as digital input port or fuel level sensor; input port 5 can be set as digital input port or programmable sensor. It can be flexibly applied in different occasions.
➢ Multiple temperature, pressure, fuel level sensor can be used and self-defined directly.
➢ With one programmable sensor can be configured as temperature, pressure or liquid level sensor. It has achieved double temperature, pressure or liquid level sensor detections.
➢ Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are optional.
➢ With emergency start function.
➢ With flywheel tooth number automatic recognition function.
➢ Widely power supply range DC(8~35)V, suitable for different starting battery voltage environment.
➢ All parameters used digital adjustment, instead of conventional analog modulation with normal potentiometer, more reliable and stable.
➢ With maintenance function. Types (date or running time) can be optional an