Technical Parameters:
Operating Voltage Range: DC10V ~ DC35V continuous power supply, DC reverse connection protection
AC Frequency Range: 10Hz~75Hz
Speed Sensor Voltage Range: 1V~ 24V(RMS)
Fuel Output 10A DC24V DC power supply output
Start Output 10A DC24V DC power supply output
Aux. Output 1 5A DC24V DC power supply output
Aux. Output 2 5A DC24V DC power supply output
Aux. Output 3 5A DC24V DC power supply output
Aux. Output 4 5A AC250V volts free output
Aux. Output 5 5A AC250V volts free output
Case Dimensions CHP150D: 136mm x110mmx46mm (Panel Mounting)
CT Secondary Current Rated: 5A
Working Temperature (-40~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-40~+70)°C
Protection Level CHP150D HMU8-CHP:IP65
Insulation Apply AC2.2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min.
Product Overview:
CHP150 Combined Heat and Power Controller integrates digitalization, intelligent and networking technology, and adopts the split mode of 【master control + display】. It is suitable for the automation and monitoring system of single unit, realizing the automatic start/stop, data measurement, alarm protection and “three remotes” functions of genset.
CHP150 Combined Heat and Power Controller adopts MPU technology, realizes a variety of parameters of precision measurement, fixed value regulation, timing, and threshold setting functions. The parameters can be adjusted from front panel of the controller, also can by USB interface or ETHERNET interface of PC. It can be widely used in various types of gensets for its compact structure, simple wiring and high reliability. CHP150D Display Module adopts LCD, which can run reliably in the temperature range of (-40℃ ~+70℃). The optional Chinese and English interfaces can display with simple operation and reliable running.
HMU8-CHP Display Module adopts 8-inch capacitive touch screen with 800*600 resolution, optional Chinese and English interfaces, which is simple to operate and reliable to run. The master control module equipped with SAE J1939 interface can communicate with diversified ECU (ENGINE CONTROL UNIT) with J1939 interface.
PERFORMANCE AND CHARACTERISTICS
CHP150 controller is applicable for automatic CHP system of single unit. It can control genset start/stop by remote signal. The CHP150 controller is consisted of two parts: CHP150M (Master Control Module) and CHP150D/HMU8-CHP (Display Module). Its main characteristics are as follows:
——The master control module has communication interfaces of ETHERNET and RS232 that can connect with display module or monitoring system;
——With 3 valves PID control functions; 2 on-off valves and a 4-20mA valve;
——The CAN BUS interface can connect to J1939 ECU, it not only can monitor the common data (water temperature, oil pressure, speed, fuel consumption, etc.) of ECU, but also can control start/stop and high/low speed through CANBUS interface;
——Suitable for 3P4W, 3P3W, 1P2W, 2P3W (120V/240V) power supply 50Hz/60Hz system;
——Collect and display parameters of Gen 3-phase voltage, 3-phase current, frequency and power parameters.
——Gen with over/under voltage, over/under frequency, over current, over power functions;
——Precisely collect various parameters of engine;
——Control and protection functions: to realize the automatic start/stop of genset, close/open and perfect fault display protection functions;
——With ETS Solenoid Hold, idle speed control, preheat control, speed up/down control functions, and they are all relay outputs;
——Parameter setting function: allow the users to change and set the parameters, while keep in the internal FLASH memorize and will not be lost when the system is power off. All the parameters can be adjusted from the front panel of the control or by USB interface of PC;
——With 7 flexible sensors and can customize the parameters;
——Multiple conditions of crank disconnect (speed sensor, oil pressure, Gen) to select;
——With emergency start function: it can be realized by input port` (manually forced start), which is used in cold winter and needs to be manually start for a long time;
——Automatic identification function of flywheel tooth number;
——Wide power supply range (8~35)VDC, which can adapt to different starting battery voltage environment;
——All parameters adopt digital adjustment, abandoning the analog adjustment method of common potentiometer, and improving the reliability and stability of the whole machine;
——Maintenance function is dived into date and running time, and the maintenance time due action can be set (warning and alarm shutdown);
——Event log can circularly record 99 items;
——Data analysis function can circularly record 5 items of detailed data a minute before the shutdown alarm;
——With RTC and scheduled start/stop functions (start once monthly/weekly/daily and set whether to take load or not).